Content on this page from the web site of Jim Lux

Rod Gap Breakdown Voltage Tables 

Table values valid for:

1.27 cm square rods
27 deg C
760 torr
15.5 torr water vapor pressure
11 g/cc water content for impulses.

Rod Gap1/5 uSec1/5 uSec1/50 uSec1/50 uSec
SpacingVoltagePos impulseNeg impulsePos impulseNeg impulse
226
447
662
872
10811011119097
15102
20124179208160178
25147
30172256301226262
40225348392279339
50278431475334407
60332513557397470
70382
80435657701511585
90488
100537820855629703

Humidity Correction

H20 Vapor Pressure (torr)2.551015202530
Correction Factor %-16.5-13.1-6.5-0.54.47.910.1

 

Rod Gap procedures and construction


Copyright 1998, Jim Lux / rodv.htm / 8 March 1998 / Back to HV Home / Back to home page / Mail to Jim