This page has some actual measurements and calculations on GE Type 5021G10 transformer, which was originally intended for an illumination power supply for a copier. It has a lot of leakage reactance to limit the current. The nominal specs are 120V input, 4500V output, 400mA short circuit output current. This transformer is interesting because it has a third winding, nominally 600V, for connecting a capacitor for power factor correction. At rated output, this transformer draws about 8.5Amps, i.e. about 1kVA
Open Circuit Tests
Short Circuit Tests
Calculated:
Reactive Power 585.9 Vars
Magnetizing Circuit R: 200 + j23.76 Ohms
Series equivalent: 1.628+j13.5 Ohms
Copyright 1997, Jim Lux / xfmrex1.htm / Back to transformer measurements /Back to HV Home / Back to home page / Mail to Jim